Configuration Mode Settings (continued)
5. Stage 1 Differential (1°F to 3°F) (1°C to 2°C) – Set the number of degrees between your “turn
on” temperature and your “setpoint” temperature.
Press the
or button to set differential value.
Press the
button to advance to the next screen.
7. Deadband (1°F to 9°F) (1°C to 5°C) – Set the minimum number of degrees between your
heating system activation and your cooling system activation.
Press the
or button to set deadband value.
Press the
button to advance to the next screen.
6. Stage 2 Differential (1°F to 6°F) (1°C to 3°C) – Set the number of degress between when Stage
1 turns on and when Stage 2 turns on.
Press the
or button to set differential value.
Press the
button to advance to the next screen.
4. Temperature scale (F or C) – Choose Fahrenheit or Celsius.
Press the
or button to select.
Press the
button to advance to the next screen.
8. Staged off outputs – Select whether the outputs for heating and cooling are staged off
independently or are satisfied simultaneously.
1 = Economy Mode – Outputs are staged on and off in accordance with setpoint and
differential.
0 = Comfort Mode – Outputs are staged on and all stages cycle off simultaneously when set
point is satisfied.
Press the
or button to select.
Press the
button to advance to the next screen.
9. Fan ON Delay – HEAT cycle (0-120 seconds) – Time fan is delayed turning ON at start of heat
cycle. For no delay, set to 0:00 (appears only for heat pump or electric heat systems).
Press the
or button to set delay.
CAUTION!: Changing from the default of 0:00 may permanently damage your system.
Press the
button to advance to the next screen.