General Data
Nominal Sizes 6 Tons [21.1 kW] ASHRAE 90.1-2004 Compliant Models
[ ] Designates Metric Conversions
Model MPS- 006AGYL13E
Cooling Performance
1
Gross Cooling Capacity Btu [kW] 75,000 [22]
EER/SEER
2
10.3/NA
Nominal CFM/ARI Rated CFM [L/s] 2400/2400 [1133/1133]
ARI Net Cooling Capacity Btu [kW] 72,000 [21.1]
Net Sensible Capacity Btu [kW] 53,000 [15.5]
Net System Power kW 7
Heating Performance (Package Gas/Electric)
4
Heating Input Btu [kW] 135,000 [39.6]
Heating Output Btu [kW] 109,400 [32.1]
Temperature Rise Range ˚F [˚C] 30-60 [16.7/33.3]
Net Weight lbs. [kg] 608 [276]
Steady State Efficiency (%) 81
AFUE % 80
No. Burners 6
No. Stages 1
Gas Connection Pipe Size in. [mm] 0.5 [12.7]
Compressor
Qty./Type 2/Scroll
Outdoor Sound Rating (dB)
5
83
Outdoor Coil—Fin Type Louvered
Tube Type Rifled
Tube Size in. [mm] OD 0.375 [9.5]
Face Area sq. ft. [sq. m] 16.56 [1.54]
Rows / FPI [FPcm] 2 / 22 [9]
Net Latent Capacity Btu [kW] 19,000 [5.6]
Indoor Coil—Fin Type Louvered
Tube Type Rifled
Tube Size in. [mm] 0.375 [9.5]
Face Area sq. ft. [sq. m] 6.5 [0.6]
Rows / FPI [FPcm] 4 / 12 [5]
Refrigerant Control Capillary Tubes
Drain Connection No./Size in. [mm] 1/1 [25.4]
Outdoor Fan—Type Propeller
No. Used/Diameter in. [mm] 1/24 [609.6]
Drive Type/No. Speeds Direct/1
CFM [L/s] 4000 [1888]
No. Motors/HP 1 at 1/3 HP
Motor RPM 1075
Indoor Fan—Type FC Centrifugal
No. Used/Diameter in. [mm] 1/11x12 [279.4x304.8]
Drive Type/No. Speeds Belt/Variable
No. Motors 1
Motor HP 1
1
/2
Motor RPM 1725
Motor Frame Size 56
Filter—Type Disposable
Furnished Yes
(No.) Size Recommended in. [mm] (4)2x16x16 [51x406x406]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 88/88 [2495/2495]
Weights
Ship Weight lbs. [kg] 615 [279]
Integrated Part Load Value
3
11.5
006AGYM13E
75,000 [22]
10.3/NA
2400/2400 [1133/1133]
72,000 [21.1]
53,000 [15.5]
7
135,000 [39.6]
109,400 [32.1]
30-60 [16.7/33.3]
608 [276]
81
80
6
1
0.5 [12.7]
2/Scroll
83
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
19,000 [5.6]
Louvered
Rifled
0.375 [9.5]
6.5 [0.6]
4 / 12 [5]
Capillary Tubes
1/1 [25.4]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/11x12 [279.4x304.8]
Belt/Variable
1
1 1/2
1725
56
Disposable
Yes
(4)2x16x16 [51x406x406]
88/88 [2495/2495]
615 [279]
11.5
NOTES:
1. Cooling Performance is rated at 95° F ambient, 8 F entering dry bulb, 67° F entering wet bulb. Gross capacity does
not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable
for operation to
20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment
certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 8 F ambient,
8 F entering dry bulb, and 67° F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions
using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations
above 2000 feet, ratings
should be reduced at the rate of 4% for each 1000 feet above sea level.
5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.