EasyManuals Logo

McQuay MCK Service Guide Book

McQuay MCK
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
28
Multi Split Conversion
Cooling Only Model (L2.0 / L208A)
The cooling only model WM-G, CK-A/B/C, CE-E, CC-C which are using L2 control board can be
switched to multi split units without any modification needed.
Heatpump Model (L2.0 / L208A)
WM-GR
The Multi Split mode can be selected at the slide switch on the On/Off Switch Board; Preset
at OFF.
The outdoor coil sensor has to be removed from the PCB as the reading is taken from the
outdoor PCB directly.
CK-AR/BR/CR, CE-ER, CC-CR
The Multi Split mode can be selected by disables the outdoor coil sensor and replace with a
dummy resistor 4.7kOhm (provided in the accessory bag).

Other manuals for McQuay MCK

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay MCK and is the answer not in the manual?

McQuay MCK Specifications

General IconGeneral
BrandMcQuay
ModelMCK
CategoryAir Conditioner
LanguageEnglish

Related product manuals