78 Service Manual SM-MDS_(ii)
High/low pressure switch trip error
Error Code: Decorative Error code #6, H4, H6, L1, 34, 41 (For MC301), E7, H1, L1 (For MDOM PCB), ER52 to
ER53, ER56 (For MDS-M PCB)
Is the coil sensor
and pressure sensor
correctly connected?
Ensure no obstacle around the unit
and conduct inspection on coil and
filter
Connect correctly and operate
again
Measure discharge /
suction pressure.
Within spec?
Is the coil sensor and
pressure sensor resistance
characteristics normal?
Refer Appendix 7.3 & 7.5
Check on power supply and wiring
connection. Replace outdoor fan
motor if necessary
Is the pressure
switch functioning?
Is the EXV working
properly?
Check for any leakage. Release or
charge the unit with refrigerant
according to specification
Outdoor fan motor working?
Is the pressure port
on OD PCB abnormal?
Is the outdoor ball
valve open/close
normally?