HEATER STAND AND LOCATION
The heater is primarily for outdoor use only.
Always ensure that adequate fresh air
ventilation is provided.
Always maintain proper clearance to
combustible materials, i.e. top 2m and sides
2m minimum. Heater must be placed on
level firm ground.
Never operate heater in an explosive
atmosphere like areas where gasoline or
other flammable liquids or vapors are
stored.
To protect heater from strong wind, anchor the base securely to the ground with
screws.
GAS REQUIREMENTS
For use with LP Gas mix only.
LP Gas regulator must be a 2, 8kPa regulator that complies with the requirements of
SANS1237.
The hose assembly to be used must conform to local standard codes.
The installation must conform to local codes, or in the absence of codes, with the
standard for storage and handling of liquid petroleum gases. SANS 1539:2012
A dented, rusted or damaged LP gas cylinder may be hazardous and should be
checked by your cylinder supplier.
Never use a LP gas cylinder with a damaged valve connection.
The LP gas cylinder must be arranged to provide for vapor withdrawal from the
operating cylinder.
Never connect an unregulated LP gas cylinder to the heater.