500 V. Analogue Insulation & Continuity Testers
M BM100/4 and BM101/4
User Guide
Guide de l’utilisateur
Gebrauchsanleitung
Guía del usuario
SAFETY WARNINGS
Safety Warnings and precautions m u s t be read and
understood before the instrument is used. They m u s t
be observed during use.
The circuit under test must be de-energised and
isolated before Insulation, Resistance, or Continuity
tests are made.
During an insulation test, the circuit must not be
touched.
After insulation tests, capacitive circuits must be
allowed to discharge before disconnecting the test
leads.
Test leads, including prods and crocodile clips must
be in good order; clean, and with no broken or
cracked insulation.
Replacement fuses must be of the correct type and
rating.
BM 100/4 Only
U.K. Safety Authorities recommend the use of fused
test leads when measuring voltage on high energy
systems.
When making a voltage measurement, the 'Test' push
must not be pressed.
NOTE
T H E I N S T R U M E N T S M U S T O N Y B E U S E D B Y S U I TA B LY T R A I N E D A N D C O M P E T E N T P E R S O N S
.
Symbols used on the instrument
Caution: Refer to accompanying notes.
Equipment protected throughout by Double Insulation
(Class II).
Equipment complies with relevant EU Directives
Question and Answer IconNeed help?

Do you have a question about the Megger BM101/4 and is the answer not in the manual?

Megger BM101/4 Specifications

General IconGeneral
DisplayAnalogue
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
TypeInsulation Tester
Insulation Resistance Measurement Range0.01 MΩ to 2000 MΩ
Continuity Range0.01 Ω to 100 Ω
Test Current1 mA
Battery TypeAlkaline
Weight1.5 kg
Voltage Range500V, 1000V

Summary

Safety Warnings

Operation Procedures

Preliminary Test Lead Check

Inspect test leads before each use for condition and insulation integrity.

Continuity Testing Procedure

Set range, connect leads, press test, read scale, release test.

Insulation Testing Procedure

Set range, connect leads, press test, read scale, allow discharge.

Resistance Testing Procedure (BM101/4)

Set range, connect leads, press test, read scale, release test.

Repair and Warranty Information

Consignes de Sécurité (French)

Essais (French)

Procédure d'essai d'isolement

Steps for performing insulation tests on the instrument.

Procédure d'essai de continuité

Steps for performing continuity tests on the instrument.

Procédure d'essai de résistance (BM101/4)

Steps for performing resistance tests on the BM101/4.

Gebrauchsanleitung (German)

Hinweise zur Betriebssicherheit

Operating safety instructions and precautions must be read and understood.

Prüfungen (German)

Guía del usuario (Spanish)

Avisos de Seguridad

Safety precautions and warnings must be read and understood before use.

Comprobaciones (Spanish)

Related product manuals