EasyManua.ls Logo

meitav-tec MTS/SUPER - Page 23

Default Icon
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4. Technician settings (cont’)
-23 -
P30 – Beeper ON or OFF
“01” - Beeper ON (default)
“00” - Beeper OFF
P31 Fan ON delay in cooling (seconds)
Range: 0…120 seconds
Default: 0 seconds (no delay)
P32 – Fan OFF delay in cooling (seconds)
Range: 0…120 seconds
Default: 0 seconds (no delay)
P33 Fan ON delay in heating (seconds)
Range: 0…120 seconds
Default: 0 seconds (no delay)
P34 – Fan OFF delay in heating (seconds)
Range: 0…120 seconds
Default: 30 seconds
P27 – Time on-delay between heating stages
Range: 0…600 seconds
Default: 5 seconds
P28 – Time off-delay between heating stages
Range: 0…600 seconds
Default: 1 seconds

Related product manuals