Press the button to return to parameter P1 or wait 60
seconds to exit technician settings and return to normal display.
P200 – Restore defaults
Press the button to restore defaults
Press the button twice to return to normal display
4. Technician settings (cont’)
-33 -
P116 – Cool PID Ki (FC only!)
Range: 0...100%
Default: 0%
P117 – Heat PID Ki (FC only!)
Range: 0...100%
Default: 0%
P118 – Cool PID Kd (FC only!)
Range: 0...100%
Default: 1%
P119 – Heat PID Kd (FC only!)
Range: 0...100%
Default: 1%