85-03-01136 ML39 Page 64
Vent Damper Adjustments
This fireplace is equipped with a vent damper system that can be adjusted using the glass latch tool. Locate damper adjustment
rod above the glass frame in convection chamber at the center. If this fireplace’s vent is terminated horizontally, DO NOT CLOSE
the vent damper completely. Adjust position of damper by judging the flame characteristics after 20 minutes of burn time. If the
flames ghost off burners or if sooting occurs [in LPG units], open the vent damper FULLY and work backwards in increments to
determine the correct damper position for that particular installation.
To adjust the damper look into the convection air cavity and note the Damper Position Indicator. Hook glass latch tool in the
hole at the end of the damper rod, pull outward about 1/8” and turn clockwise to close the vent damper, release. The base of
the damper adjustment rod has a pointer that indicates the position of the damper.