| primary power | 12 to 24Vdc ±10%, 350mA maximum |
|---|---|
| 12Vdc power consumption | 300mA nominal |
| 24Vdc power consumption | 220mA nominal |
| outputs quantity | 2 outputs |
|---|---|
| output type | Form-C |
| output current rating | 5A @ 28Vdc, resistive |
| unsupervised/supervised inputs | 16 |
|---|---|
| standard EOL | 1k/1k ohm, 1%, 1/4 watt |
| dedicated inputs for tamper and fault monitoring | 2 |
| communication interface | RS-485, 2-wire |
|---|---|
| communication speeds | 9600, 19200, 38400, or 115200 bps |
| RS-485 cable requirements | 24AWG, 120 ohm impedance, twisted pair with shield |
| dimensions | 6" (152mm)W x 8" (203mm)L x 1" (25.4mm)H |
|---|---|
| weight | 9 oz. (250 g) nominal |
| power cable requirements | 18 AWG, 1 twisted pair |
| storage temperature range | -55°C to +85°C |
|---|---|
| operating temperature range | 0°C to +70°C |
| humidity tolerance | 0% to 95% RHNC |
Configures the RS-485 interface for 2-wire or 4-wire operation, specifying jumper J3 installation.
Installs jumper J1 for 120 ohm line termination at the end of the RS-485 communication line.
Recommends diode selection for protection circuits for inductive loads connected to relay outputs.
Recommends MOV selection for protection circuits for inductive loads connected to relay outputs.
Details the function and usage of various jumpers (J1-J9) for MR16in configuration and operation.