WARNING
This appliance must be earthed. Failure to do so may result in electric shock and death.
Mealstream EC401EE5, RD401 (13A) UK models
The electricity supply lead is located at the rear of the oven.
AllUKmodelsaresuppliedwithattedandapproved13
amp moulded plug. We strongly recommend that this plug is
never removed. However certain establishments may require
adifferentplugtobetted.Inthiscase,thefollowingwiring
instructions should be observed
Newplugsshouldonlybettedbyaqualiedelectrician.
The power outlet used must be individually fused at 13 Amps.
It is essential that the socket is properly installed and earthed.
It should be fed from a circuit which is suitable for high power
electrical appliances and it is important that this circuit is not
overloaded.
Warning: Never use extension leads or adaptors.
Mealstream EC401XX5 EC401XE5, RD401XE, EC403XE, EC403XX5 (30A)
The Mealstream EC401 & RD401 ( 30A ) must be connected to a separate electrical supply rated at 30 Amps by
aqualiedandapprovedelectrician.Asuitable30ampratedisolatingswitchwitha3mmcontactgaponboth
polesshouldbettedforeachoveninstalled.
Establishments with standard ( Type ‘B’ ) circuit breakers are sensitive to ‘surges’ which occur on switching on
freezers, refridgerators and other catering equipment, including microwave ovens. Because of this, we strongly
recommendthataseparateType‘C’circuitbreaker(designedspecicallyforthistypeofequipment)mustbe
tted.Anindividual,suitablyratedcircuitbreakershouldbettedforeachoveninstalled.
If you are in any doubt about your electrical
supply,seektheadviceofaqualiedelectrician
WARNING
SINGLE PHASE
TWIN PHASE
The Mealstream 401 oven Twin Phase models should be
connected as shown.
The Circuit Breaker should be rated at 16amps/ phase
(TypeC).
SINGLE PHASE
UKmodelsarettedwithaBlue32AmpPlugto
BS EN 60309.2
The Circuit Breaker should be rated at 45A (TypeC).
TWIN PHASE
This equipment complies with EN61000-3-11 when connected to a mains supply having a maximum impedance
(Z
max
) of 0.35ohms.
The user should determine in consultation with the supply authority, if necessary, that the equipment is connected
only to a supply of Z
max
or less.
ELECTRICAL SUPPLY
EC401XX5 & EC403XX5 models only