UNT Controller—Unitary Controller (UNT) 91
Appendix B: UNT100/101
This section contains information specific to the discontinued
UNT100/101. To troubleshoot the UNT100/101, refer to the
Troubleshooting section of this technical bulletin.
The following list contains features of the UNT100/101 which differ from
the other UNT types.
No earth ground connections are allowed when wiring a
UNT100/101 series controller.
The N2 bus is not isolated. The secondary of the 24 VAC transformer
cannot be grounded.
The BIs can accept dry contacts only, not 24 VAC. They can also
accept 100 Hz as accumulator input.
The BO is not jumper selectable. The triac switches to the common
side of 24 VAC only.
untrm100
BINARY IN BINARY OUTPUTS
%,1$5< ,1
$1$/ 2* , 138 76
 
$1$/ 2 * , 13876
&20 021
%,1$5< &20
9'&
&20
3:5
,1
9
$&
%,1$5< 287387
9$& 72 /2$'6


9'&
$1$ /2*
287387
$1$/ 2*
287387
&2 0021
70
OFF
1 2 3 4 5 6 7 8
AS-UNT101-0
+
-
BINARY OUTPUTS
BINARY INANALOG INPUTS
TO ZONE STAT
ZBUS
AREF
NA+
NA-
24VAC
COMMON
24VAC
POWER
Figure 41: UNT100 Terminal Designations
What’s Different
About the
UNT100/101
UNT100/101
Terminal
Designations