Table 11 ņ Menu Structure (cont)*
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment
Notes
CHECKOUT
DAMPER VMIN .HS n/a n/a Positions OA damper to VMIN High Speed position
'$03(590$;+6 n/a n/a 3RVLWLRQV2$GDPSHUWR90$;+LJK6SHHGSRVLWLRQ
DAMPER OPEN n/a n/a Positions OA damper to the full open position.
DAMPER CLOSE n/a n/a Positions damper to the fully closed position
CONNECT Y1---O n/a n/a Closes the Y1---O relay (Y1---O)
CONNECT Y2---O n/a n/a Closes the Y2---O relay (Y2---O)
&211(&7$8;2 n/a n/a (QHUJL]HVWKH$8;2RXWSXW,I$X[VHWWLQJLV
• NONE --- not action taken
• ERV --- 24 Vac out. Turns on or signals an ERV that the
conditions are not good for economizing but are good for ERV
operation.
d
• 6<69DFRXW,VVXHVDV\VWHPDODUP
ALARMS(_)
Alarms display only when they are active. The menu title “ALARMS(_)”
includes the number of active alarms in parenthesis ( ).
MA T SENS ERR n/a n/a 0,;('$,57(03(5$785(6(1625(5525
CO2 SENS ERR n/a n/a CO2 SENSOR ERROR
OA T SENS ERR
n/a n/a OUTSIDE AIR TEMPERATURE SENSOR ERROR
OAT sensor connected at input terminals OAT
OA SYLK SENS ERR
n/a n/a OUTSIDE AIR ENTHALPY SENSOR ERROR
2$7VHQVRUFRQQHFWHGRQ6EXV
DA T SENS ERR
n/a n/a DISCHARGE AIR TEMPERATURE SENSOR ERROR
SYS ALARM
n/a n/a :KHQ$8;LVVHWWR6<6DQGWKHUHLVDQ\DODUPHJIDLOHG
VHQVRUVHWFWKH$8;WHUPLQDOSURYLGHV9DFRXW
ACT UNDER V
n/a n/a ACTUATOR VOLTAGE LOW
Voltage received at actuator is below expected range
ACT OVER V
n/a n/a ACTUATOR VOLTAGE HIGH
Voltage received at actuator is above expected range
ACT STALLED
n/a n/a
ACTUATOR STALLED
Actuator stopped before reaching commanded position
*Table 11 illustrates the complete hierarchy. your menu parameters may be different depending on your configuration.
LEGEND
LCD Liquid Crystal Display
MAT Mixed Air Temperature
OAT Outdoor Air Temperature
OCC Occupied
RAT Return Air Temperature
RTU Rooftop Unit
CHECKOUT TESTS
Use the Checkout menu (see Table 11) to test the damper operation
DQG DQ\ FRQ¿JXUHG RXWSXWV 2QO\ LWHPV WKDW DUH FRQ¿JXUHG are
shown in the Checkout menu.
NOTE: See User Interface for information about menu navigation
and use of the keypad.
To perform a Checkout test:
6FUROOWRWKHGHVLUHGWHVWLQWKH&KHFNRXWPHQXXVLQJWKHŸ
DQGźEXWWRQV
2. Press the button to select the item.
3. RUN? appears.
4. Press the button to start the test.
5. The unit pauses and then displays IN PROGRESS.
:KHQWKHWHVWLVFRPSOHWH'21(DSSHDUV
7. When all desired parameters have been tested, press the
Ĺ0HQXXSEXWWRQWRHQGWKHWHVW
Checkout test can be performed at any time during the operation of
the system as a test that the system is operable.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage to equipment
Be sure to allow enough time for compressor startup and
shutdown between checkout tests so that you do not short-cycle
the compressors.
!