EasyManua.ls Logo

Midea 11MSFI-A2-1301

Midea 11MSFI-A2-1301
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16
6.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas
Liquid
MS11MU-09HRFN1-QRD0W+ MOC-09HFN1-QRD0W
3/8’’
(Ф9.52)
1/4’’
(Ф6.35)
5
8
20
20
MS11M-09HRFN1-QRD1W(A)+ MOC-09HFN1-QRD1W
5
8
20
20
MS11MU-12HRFN1-QRD0W+ MOC-12HFN1-QRD0W
5
8
20
20
MS11M-12HRFN1-QRD1W(A)+ MOC-12HFN1-QRD1W
5
8
20
20
MS11MU-12HRFN1-QRD0W(B)+ MOC1-12HFN1-QRD0W
5
8
20
20
MS11MU-18HRFN1-QRC8GW+MOC-18HFN1-QRC8W
1/2’’
12.7)
1/4’’
(Ф6.35)
5
10
25
20
MS11M1-24HRDN1-QRC8W+MOF-24HFN1-QRC8W
5/8’’
15.9)
3/8’’
(Ф9.52)
5
10
25
40
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.
The oil trap should be installed per 5-7 meters.

Related product manuals