If users switch on AC by remote controller, the compressor will run at the Fmax frequency for 7
minutes according to outdoor ambient temp. During the 7 minutes, the frequency limitation is active.
7 minutes later, the compressor running frequency will be controlled as below:
While the zones of A,B,C... are corresponding to different compressor running frequency.
ΔT=0℃ as default.
Note:
When T1-Ts keeps in the same temp. zone for 3 minutes, the compressor will run as the below rules:
A: Increase the frequency to 3 grade higher until to FREMAX.
B~E: Increase the frequency to 2 grade higher until to FREMAX.
F~G: Increase the frequency to 1 grade higher until to FREMAX.
H: Keep the current frequency.
I: Decrease the frequency to the 1 grade lower until to F1.
J: Run at F1 for 1h.(if T1-Ts -ΔT >6℃, the compressor will stop)