Auxilliary Heater Electrical Data
208/230V
CIRCUIT 1 CIRCUIT 2 CIRCUIT 3
Heater Part
No.
Heater
kW
Internal
Circuit
Protection
Heater
Amps
MCA (1) MOCP (2)
Heater
Amps
MCA (1) MOCP (2)
Heater
Amps
MCA (1) MOCP (2)
EAH-03B(UL)
3 Ckt Bkr
10.8/12.0 14.0/16.0 15.0/20.0
// / / / /
EAH-05B(UL)
5 Ckt Bkr
18.0/20.0 23.0/27.0 25.0/30.0
// / / / /
EAH-08B(UL)
8 Ckt Bkr
28.8/32.0 37.0/42.0 40.0/45.0
// / / / /
EAH-10B(UL)
10 Ckt Bkr
36.0/40.0 46.0/53.0 50.0/60.0
// / / / /
EAH-15B(UL)
15 Ckt Bkr
18.0/20.0 23.0/27.0 25.0/30.0 36.0/40.0 46.0/53.0 50.0/60.0
// /
EAH-20B(UL)
20 Ckt Bkr
36.0/40.0 46.0/53.0 50.0/60.0 36.0/40.0 46.0/53.0 50.0/60.0
// /
EAH-25B(UL)
25 Ckt Bkr
18.0/20.0 23.0/27.0 25.0/30.0 36.0/40.0 46.0/53.0 50.0/60.0 36.0/40.0 46.0/53.0 50.0/60.0
Indoor Unit
Installation
(1) Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25
(2) Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps