Page 50
Specification
Cold Climate Heat Pump
1
MCA: Minimum Circuit Ampacity / MOCP: Maximum Over Current Protection
Series
Cold Climate Heat Pump
Midea Outdoor Unit Model:
MOX43OU-
18HFN1-M
MOD3O-
24HFN1-MW
MOD30U-
30HFN1-MRO(X)
MOE31U-
36HFN1-M
MOE30U-
48HFN1-M-(X1)
Power supply Rated
V, Ph, Hz
208/230V, 1, 60
MCA/MOCP
1
A 16.0 / 20.0 20.5 / 35.0 23.0 / 35.0 41.0 / 50.0 42.0 / 50.0
Cooling
Rated capacity (range)
Btu/h
18000
(6880-21000)
24000
(6400-27000)
30000
(10400-33600)
36000
(12000-47400)
47000
(18000-48000)
EER
Btu/W
12.5 12.5 11.0 10.5 8.5
SEER
Btu/W
20.0 20.0 18.0 18.0 16.0
Heating at 47°F (8.3°C)
Rated capacity (range)
Btu/h
19000
(2800-21000)
24000
(10100-31000)
33000
(12000-37000)
40000
(9000-57200)
50000
(20000-55000)
HSPF4
Btu/W
11.0 12.0 10.5 10.5 10.0
HSPF5
Btu/W
9.0 10.0 8.4 8.5 8.5
Heating at 5°F (-15°C)
C
apacity
Btu/h
19000 24000 28500 43300 47000
COP W/W
1.90 1.80 1.95 1.80 1.88
Outdoor noise level (Sound pressure) dB(A) 58.0 64.0 61.5 64.0 64.0
Throttle type EEV for Heating
Outdoor unit
Dimension (WxDxH)
in
35.04x13.46x26.50 37.24x16.14x31.89 37.24x16.14x31.89 37.48x16.34x52.48 37.48x16.34x52.48
Packing (WxDxH)
in
39.17x15.67x29.13 42.91x19.69x34.84 42.91x19.69x34.84 43.11x19.49x58.27 43.11x19.49x58.27
Net/gross weight
lbs 102.95/109.79 136.69/145.50 159.83/169.75 227.07/255.73 220.24/248.90
Refrigerant
piping
Liquid side/gas side
in 3/8 / 3/4 3/8 / 3/4 3/8 / 3/4 3/8 / 3/4 3/8 / 3/4
Max. pipe length ft 98 164 213 213 213
Max. difference in level
ft 66 82 98 98 98
Ambient
temperature
Cooling °F (°C) -22 ~ 122 (-30 ~ 50)
Heating °F (°C) -22 ~ 75 (-30 ~ 24)
Qty per 20’/40’/40’ HQ Outdoor unit 99/198/198 44/96/144 44/96/144 22/48/48 22/48/48
Certification
Performance
AHRI Yes
E*Star Yes Yes - - -
NEEP Yes
Safety
UL Yes
ETL -
CSA -