Atom B Series VRF 50/60Hz
56
Midea
Atom B
Series
Service Manual
2.8 E9: EEPROM error (For all models)
2.8.1 Digital display output
E9
2.8.2 Description
EEPROM error
The system stops running.
Error code is displayed on the outdoor unit PCB.
2.8.3 Trigger / recover condition
Trigger condition: Unable to read the EEPROM when startup.
Recover condition: EEPROM goes back to normal.
Reset method: Manually restart.
2.8.4 Possible causes
The EEPROM is not inserted well
Damaged main PCB.
2.8.5 Procedure
E9
Check whether the EEPROM is inserted well.
No
Insert the EEPROM well
Yes
Replace outdoor main PCB.

Related product manuals