Atom B Series VRF 50/60Hz
57
Part
6
-
Diagnosis and Troubleshooting
2.9 E.9.: Compressor parameters mismatch (For all models)
2.9.1 Digital display output
E.9.
2.9.2 Description
Main control chip detect the power setting number mismatch the model, the unit will display E.9. error.
The system stops running.
Error code is displayed on the outdoor unit PCB.
2.9.3 Trigger / recover condition
Trigger condition: Main control chip detect the power setting number mismatch the model.
Recover condition: Main control chip detect the power setting number match the model.
Reset method: Manually restart.
2.9.4 Possible causes
Power number setting mistake.
Damaged main PCB.
2.9.5 Procedure
E.9.
Confirm whether the power setting number is
corresponding with the outdoor unit
1
No
Power off and reset the
power number
Yes
Replaced outdoor main control board
Notes:
1. Power setting switch is only for 36-56 model; 28 model don’t need to setting