2.10 EF: PFC fault (For all models)
2.10.1 Digital display output
EF
2.10.2 Description
PFC fault protection.
The system stops running.
Error code is displayed on the outdoor unit PCB.
2.10.3 Trigger / recover condition
Trigger condition: DC bus voltage is over 450V for continue 3 S or over 500V in the first 5 s in PFC star period.
Recover condition: DC bus voltage is normal in the first 5 s in PFC star period.
Reset method: Manually restart.
2.10.4 Possible causes
DC fan motor damaged.
Main PCB damaged.
2.10.5 Procedure