Atom B Series VRF 50/60Hz
59
Part
6
-
Diagnosis and Troubleshooting
2.11 EH: Refrigerant radiator temperature sensor error (For all models)
2.11.1 Digital display output
EH
2.11.2 Description
Refrigerant radiator temperature TL sensor error.
The system stops running.
Error code is displayed on outdoor unit PCB.
2.11.3 Trigger / recover condition
Trigger condition: TL temperature sensor is open circuited (or connecter loose) or short circuited.
Recover condition: The main control board can receive a normal feedback signal of TL sensor.
Reset method: Resume automatically.
2.11.4 Possible causes
TL temperature sensor damaged.
TL temperature sensor connect to the main control board is loose.
Main PCB damaged.
2.11.5 Procedure
EH
Temperature sensor connection on main
PCB is loose
Yes
Ensure the sensor is connected properly
No
Temperature sensor has short-circuited
or failed
Yes
Replace the sensor
No
Replace outdoor main PCB