2.12 EP: Outdoor ambient temperature is lower than -15 in cooling operation (For all models)
2.12.1 Digital display output
EP
2.12.2 Description
Outdoor ambient temperature is lower than -15 in cooling operation.
The system stops running.
Error code is displayed on outdoor unit PCB.
2.12.3 Trigger / recover condition
Trigger condition: Outdoor ambient temperature is lower than -15 in cooling operation.
Recover condition: Outdoor ambient temperature is over -15.
Reset method: Resume automatically.
2.12.4 Possible causes
TL temperature sensor damaged.
TL temperature sensor connect to the main control board is loose.
Main PCB damaged.
2.12.5 Procedure
EP
T4 sensor detected temperature is lower
than -15
Yes
Temperature over operation range
No
T4 temperature sensor has short-
circuited or failed
Yes
Replace the T4 sensor
No
Replace outdoor main control board