2.12 EP: Outdoor ambient temperature is lower than -15℃ in cooling operation (For all models)
2.12.1 Digital display output
EP
2.12.2 Description
Outdoor ambient temperature is lower than -15℃ in cooling operation.
The system stops running.
Error code is displayed on outdoor unit PCB.
2.12.3 Trigger / recover condition
Trigger condition: Outdoor ambient temperature is lower than -15℃ in cooling operation.
Recover condition: Outdoor ambient temperature is over -15℃.
Reset method: Resume automatically.
2.12.4 Possible causes
TL temperature sensor damaged.
TL temperature sensor connect to the main control board is loose.
Main PCB damaged.
2.12.5 Procedure