Blanc On-off DM16-01.01.07en
56 Service manual
11.2.7 Refrigerant Leakage Detection diagnosis and solution(EC)
Error Code
EC
Malfunction decision
conditions
Define the evaporator coil temp.T2 of the compressor just starts
running as Tcool.
In the beginning 5 minutes after the compressor starts up, if T2
<Tcool-2℃ does not keep continuous 4 seconds and this
situation happens 3 times, the display area will show “EC” and
AC will turn off.
Supposed causes ● T2 sensor faulty
● Indoor PCB faulty
● System problems, such as leakage or blocking.
Trouble shooting: