Midea DLFLDAH36XAK - User Manual

Midea DLFLDAH36XAK
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Specifications subject to change without notice.
DLFSDA and DLFLDA
INSTALLATION INSTRUCTIONS
Ducted Style Ductless System − Sizes 09 to 58
Fig. 1 - Sizes 09−48
Fig. 2 - Size 58
NOTES:
Read the entire instruction manual before starting the installation.
Images are for illustration purposes only. Actual models may differ
slightly.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 2.............................
PARTS LIST 3...........................................
SYSTEM REQUIREMENTS 4...............................
WIRING 4...............................................
DIMENSIONS 5..........................................
INSTALLATION CLEARANCES 7...........................
MAINTENANCE CLEARANCES 7..........................
INSTALLATION LOCATION REQUIREMENTS 8..............
INDOOR UNIT INSTALLATION 8...........................
EXTERNAL STATIC PRESSURE 12.........................
FAN PERFORMANCES AT VARYING STATIC PRESSURES 13....
ELECTRICAL DATA 21...................................
CONNECTION DIAGRAMS 21.............................
START−UP 24............................................
TROUBLESHOOTING 25..................................
Question and Answer IconNeed help?

Do you have a question about the Midea DLFLDAH36XAK and is the answer not in the manual?

Summary

Safety Considerations

Electrical Shock Hazard

Warning about electrical shock during installation or servicing.

Explosion Hazard

Warning regarding explosion risk from improper gas use.

Equipment Damage Hazard

Caution about damage from incorrect pipe burial.

System Requirements

Installation Clearances

Installation Location Requirements

Installing Ductwork

Condensate Drain and Condensate Lift Pump Installation (Horizontal Installation)

External Static Pressure

Connection Diagrams

Install All Power, Interconnecting Wiring, and Piping to Indoor Unit

Start-Up

Test Operation

Procedure for performing test operation after installation.

Troubleshooting

Indoor Unit Diagnostic Guides

Guide to interpreting indoor unit diagnostic codes.

Overview

This document provides installation instructions for the DLFSDA and DLFLDA Ducted Style Ductless Systems, covering sizes 09 to 58. It includes safety considerations, parts lists, system requirements, wiring diagrams, dimensions, installation and maintenance clearances, indoor unit installation procedures, external static pressure settings, fan performance data, electrical data, connection diagrams, start-up instructions, and troubleshooting guides.

Function Description:

The DLFSDA and DLFLDA units are ducted style ductless systems designed for air conditioning. They are intended for indoor installation, typically within a false ceiling, and are connected to an outdoor unit. The system provides cooling and heating capabilities, with various fan speed settings and airflow adjustment options. Some models include a built-in condensate lift pump, while others require an external pump for horizontal installation. The units are designed to integrate with ductwork for air distribution.

Important Technical Specifications:

  • Refrigerant Line Length: Minimum 10 ft. (3 m) between indoor and outdoor units.
  • Pipe Sizes (Gas/Liquid):
    • 9K: Gas 3/8 in. (9.52 mm), Liquid 1/4 in. (6.35 mm)
    • 12K: Gas 1/2 in. (12.7 mm), Liquid 1/4 in. (6.35 mm)
    • 18K: Gas 1/2 in. (12.7 mm), Liquid 1/4 in. (6.35 mm)
    • 24K: Gas 5/8 in. (16 mm), Liquid 3/8 in. (9.52 mm)
    • 36K: Gas 5/8 in. (16 mm), Liquid 3/8 in. (9.52 mm)
    • 48K: Gas 5/8 in. (16 mm), Liquid 3/8 in. (9.52 mm)
    • 58K: Gas 3/4 in. (19 mm), Liquid 3/8 in. (9.52 mm)
  • Electrical Data (Indoor Fan):
    • 09K/12K: 1.11 FLA, 0.18 HP, 130 W
    • 18K/24K: 1.2 FLA, 0.27 HP, 200 W
    • 36K: 2.45 FLA, 0.56 HP, 420 W
    • 48K: 3.2 FLA, 0.75 HP, 560 W
    • 58K: 3.65 FLA, 0.952 HP, 1000 W
    • Voltage: 208/230-1-60 for all sizes.
  • Condensate Lift Pump:
    • External for sizes 09-18 (provided in a separate box for horizontal installation).
    • Built-in for sizes 24-58.
    • Capable of lifting water 29.5 in. (750 mm).
    • Highest point in piping should be close to the unit.
    • Drain piping slope: minimum 1/100 downward.
  • External Static Pressure (Rated Point):
    • 9K: 0.068 in. WG (17 Pa) to 0.176 in. WG (44 Pa)
    • 12K: 0.064 in. WG (16 Pa) to 0.20 in. WG (50 Pa)
    • 18K: 0.096 in. WG (24 Pa) to 0.392 in. WG (98 Pa)
    • 24K: 0.10 in. WG (25 Pa) to 0.528 in. WG (132 Pa)
    • 36K: 0.168 in. WG (42 Pa) to 0.62 in. WG (155 Pa)
    • 48K: 0.18 in. WG (45 Pa) to 0.64 in. WG (160 Pa)
    • 58K: 0.296 in. WG (74 Pa) to 0.8 in. WG (200 Pa)
  • Airflow at Rated Point (CFM/CMH):
    • 9K: High 353/600, Medium 282/480, Low 176/300
    • 12K: High 353/600, Medium 282/480, Low 176/300
    • 18K: High 529/900, Medium 450/765, Low 370/630
    • 24K: High 776/1320, Medium 694/1180, Low 435/740
    • 36K: High 1082/1840, Medium 912/1550, Low 703/1195
    • 48K: High 1229/2090, Medium 1032/1755, Low 715/1215
    • 58K: High 2157/3665, Medium 1710/2906, Low 1262/2145
  • Outside Air Connection: Knockout located downstream of the air filter. Booster fan (field supplied) recommended, powered by PCB board CN43 (max 200W input).

Usage Features:

  • Return Air Arrangement: Sizes 09-48 can be modified from rear return to bottom return by repositioning the air return flange and filters.
  • External Static Pressure Adjustment: Can be manually set to SP1, SP2, SP3, SP4 via the KSACN0501AAA Wired Controller, or automatically adjusted using the "AF" function.
  • Wired and Wireless Remote Control: Supports both wired and wireless remote controllers for operation. Wireless remote requires relocating the IR receiver for optimal line of sight.
  • Diagnostic Codes: Equipped with LEDs on both indoor and outdoor units to display diagnostic codes for troubleshooting.
  • Start-up Test Operation: Includes a procedure to perform a test operation after installation, checking functions like remote control, display panel lights, air deflection louver, and drain operation.
  • Communication Wiring:
    • Sizes 09-24: Field supplied 14/3 power/communication wiring from outdoor to indoor unit (4 wires: 2 high voltage AC, 1 communication, 1 ground). Shielded 14/2 stranded wire can be used for communication in high EMF areas.
    • Sizes 36-58: Field supplied power wiring from outdoor to indoor unit (3 wires: 2 high voltage AC, 1 ground). Separate shielded 16GA stranded control wire for communication.
    • All connections are sensitive to polarity.

Maintenance Features:

  • Clearances: Specific minimum clearances are required for installation and maintenance access (e.g., >11.8 in. (30 cm) for bottom return blower/motor service, >4 in. (10 cm) for depth of unit, >0.8 in. (2 cm) for side clearances).
  • Filter Service: Dedicated service access for air filter.
  • Blower/Motor Service: Access for servicing blower and motor components.
  • PCB Board Service: Access for servicing the PCB board.
  • Condensate Pump Maintenance: For built-in pumps (sizes 24-58), the pump can be detached by removing four screws and unplugging power/water level switch cables.
  • Drainage Test: Procedure to check for unhindered drainpipe and leaks by filling the drain pan with water.
  • Motor Maintenance: Instructions provided for taking off the ventilated panel, blower housing, and motor for maintenance.
  • Ceiling Access Panel: If installed above a hard lid ceiling, an access panel the length and width of the unit is recommended for removing blower components or the entire unit. Minimum dimensions for a single access panel are specified.

Midea DLFLDAH36XAK Specifications

General IconGeneral
RefrigerantR410A
Cooling Capacity36000 BTU/h
Heating Capacity36000 BTU/h
Indoor Unit Weight12 kg
Outdoor Unit Weight45 kg