EasyManuals Logo
Home>Midea>Air Handlers>DLFSAB Series

Midea DLFSAB Series User Manual

Midea DLFSAB Series
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
DLFSAB and DLFLAB: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
26
DIAGNOSIS AND SOLUTION (CONT.)
PC 01 - Over voltage or too low voltage protection / PC 10 - Outdoor unit low AC voltage protection / PC
11 - Outdoor unit main control board DC bus high voltage protection / PC 12 (Outdoor unit main control
board DC bus high voltage protection / 341 MCE error Diagnosis and Solution
Description: Abnormal increases or decreases in voltage are detected by checking the specified voltage detection circuit.
Recommended parts to prepare:
Power supply wires
IPM module board
•PCB
Reactor
Troubleshooting and Repair:
NOTE: For certain models, the outdoor PCB could not be removed separately. In this case, the outdoor electric control box
should be replaced as a whole.
Check the power supply.
Is it in working order? Turn o the unit.NO
Check the connections and wires .
YES
Are they in working order? NO
Power on and measure the
voltage between P and N.
YES
While the unit is in
STANDBY mode, is the
voltage between P and N and around
DC 310V, 340V or 380V?
When the unit is started,
is it in 220V~400V?
Replace the IPM board.NO
Check the reactor.
YES
Is it in working order?
Replace outdoor PCB.
NO
Replace the reactor.
YES
Ensure proper connections or
replace the wires.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea DLFSAB Series and is the answer not in the manual?

Midea DLFSAB Series Specifications

General IconGeneral
BrandMidea
ModelDLFSAB Series
CategoryAir Handlers
LanguageEnglish

Related product manuals