DLFSAB and DLFLAB: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3
AUXILLIARY CONTACTS FOUND ON THE MAIN BOARD
Work Terminal Port CN23 - Normally Open Dry Contact (Output)
•The
WORK
terminal port is linked to the unit's indoor blower
• When the indoor blower is off, the contact is open
• When the indoor blower is running, the contact is closed
• There is no voltage from CN23, power is provided from the external control system and not from the unit.
• The contacts are rated at 250VAC and 10 AMP maximum
• If an active 24V signal output is required, G and C ports (thermostat connections) may be used instead.
Fig. 1 — Auxiliary Contacts
ALARM Terminal Port CN33 - Normally Open DRY CONTACT (OUTPUT):
• Allows the terminal port to connect to an external
ALARM
interface or annunciator
• There is no voltage from
CN33
, power is provided from the
ALARM
system and not from the unit.
• The contacts are rated at
250VAC
and 10 AMP maximum
• When the unit experiences a problem, the contact closes, and the
ALARM
is triggered.
Fig. 2 — Auxiliary Contacts