DLFSAB and DLFLAB: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3
AUXILLIARY CONTACTS FOUND ON THE MAIN BOARD
Work Terminal Port CN23 - Normally Open Dry Contact (Output)
•The
WORK
terminal port is linked to the unit's indoor blower
When the indoor blower is off, the contact is open
When the indoor blower is running, the contact is closed
There is no voltage from CN23, power is provided from the external control system and not from the unit.
The contacts are rated at 250VAC and 10 AMP maximum
If an active 24V signal output is required, G and C ports (thermostat connections) may be used instead.
Fig. 1 — Auxiliary Contacts
ALARM Terminal Port CN33 - Normally Open DRY CONTACT (OUTPUT):
Allows the terminal port to connect to an external
ALARM
interface or annunciator
There is no voltage from
CN33
, power is provided from the
ALARM
system and not from the unit.
The contacts are rated at
250VAC
and 10 AMP maximum
When the unit experiences a problem, the contact closes, and the
ALARM
is triggered.
Fig. 2 — Auxiliary Contacts