EasyManua.ls Logo

Midea HB-A100/CGN8-B - Page 61

Midea HB-A100/CGN8-B
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
M thermal Split
60 202004
Midea M thermal Split
Service Manual
4.6 E5, E6, E9, EA Troubleshooting
Digital display output 4.6.1
Description 4.6.2
E5 indicates an air side heat exchanger refrigerant outlet temperature sensor error.
E6 indicates an outdoor ambient temperature sensor error.
E9 indicates a suction pipe temperature sensor error.
EA indicates a discharge temperature sensor error.
M thermal Split stops running.
Error code is displayed on outdoor unit main PCB and user interface.
Possible causes 4.6.3
Temperature sensor not connected properly or has malfunctioned.
Damaged outdoor unit main PCB.
Midea CAC
Confidential

Related product manuals