M thermal Mono
12    202008 
Midea M thermal Mono 
1 Stop Operation 
The stop operation occurs for one of the following reasons: 
1.  Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs the system makes a 'stop with 
thermo off  operation and an error code is displayed on the outdoor unit PCB and on the user interface. 
2.  The system stops when the set temperature has been reached. 
 
2 Standby Control 
2.1 Crankcase Heater Control 
The crankcase heater is used to prevent refrigerant from mixing with compressor oil when the compressors are stopped. 
The crankcase heater is controlled according to outdoor ambient temperature and the compressor on/off state. When the 
outdoor ambient temperature is above 8°C or the compressor is running, the crankcase heater is off; when the outdoor 
ambient temperature is at or below 8°C and either the compressor has been stopped for more than 3 hours or the unit has 
just been powered-on (either manually or when the power has returned following a power outage), the crankcase heater 
turns on.   
2.2 Water Pump Control 
When the outdoor unit is in standby, the internal and external circulator pumps run continuously.   
 