M‐ThermalSplit
20190945
Procedure
E2


CommunicationwiresXYEhaveshort
circuited,disconnectedorare
misconnected
1
Yes
Reconnectthecommunicationwires
No

CommunicationwiresXYEarenot
connectedinadaisychain
Yes
Connectthecommunicationwiresina
daisychain
No

WiresbetweenhydronicboxmainPCB
andelectriccontrolboxcommunication
terminalsblockareloose
Yes
Ensurethewiresareconnectedproperly
No

Interferencefromhighvoltage(220Vor
higher)wires
Yes
Ensurethecommunicationwiresand
highvoltagewiresareseparated
No

Communicationwiresareclosetoa
sourceofelectromagneticradiationsuch
astransformerorstrongfluorescentlamp
Yes
Removethesourceofinterference,or
addadditionalshieldingtothe
communicationwires
No

Replacingelectriccontrolbox
communicationterminalsblockresolves
theerror

No

ReplacehydronicboxmainPCB
Notes:
1. Measuretheresistanceamong X,Yand E.ThenormalresistancebetweenPandQis120Ω,betweenPandEisinfinite,betweenYandEisinfinite.
Communicationwiringhaspolarity.EnsurethattheXwireisconnectedtoXterminalsandtheYwireisconnectedtoYterminals.