M‐ThermalSplit
20190947
Procedure
E3/E4/H2/H3/Ed/HA/H5/H9 


Temperaturesensorconnectionon
hydronicboxmainPCBisloose
Yes
Ensurethesensorisconnectedproperly
No

Temperaturesensorhasshort‐circuited
orfailed
2
Yes
Replacethesensor
No

ReplacehydronicboxmainPCB
Notes:
1. Backupelectric heaterwateroutlettemperaturesensor,
watersideheat exchangerrefrigerantinlet(liquidpipe) temperaturesensor,watersideheat
exchangerrefrigerantoutlet (gaspipe) temperaturesensor,watersideheatexchangerwaterinlettemperaturesensorandwater sideheatexchanger
wateroutlettemperaturesensorconnectionsareportCN6onthehydronicboxmainPCB(labeled11inFigure4‐2.1inPart4,2.2"MainPCBforHydronic
System").
DomestichotwatertanktemperaturesensorconnectionisportCN13onthehydronicboxmainPCB(labeled12inFigure4‐2.1inPart4,2.2
"MainPCBforHydronicSystem").Circuit2wateroutlettemperaturesensorconnectionisportCN15onthehydronicboxmainPCB(labeled13inFigure
4‐2.1inPart4,2.2"MainPCBforHydronicSystem").RoomtemperaturesensorconnectionisportCN16onthehydronicboxmainPCB(labeled14inFigure
4‐2.1inPart4,2.2"MainPCBforHydronicSystem").
2. Measuresensor resistance.If the resistanceis toolow, the sensorhasshortcircuited.Iftheresistanceisnotconsistentwith thesensor’s resistance
characteristicstable,thesensorhasfailed.RefertoTable4‐5.1or4‐5.3inPart4,5.1“TemperatureSensorResistanceCharacteristics”.