9.4 Outdoor unit point check function   
A check switch is included on the outdoor PCB. 
Push SW1 to check the unit's status while running. The digital display shows the following codes each time 
the SW1 is pushed. 
 
Number 
of 
Presses
Display  Remark 
0  Normal display 
Displays running frequency, running state, or malfunction code
 
1  Quantity of indoor units with working connection
Actual data 
Display
Number of indoor unit
1  1 
2  2 
3  3 
4  4 
2  Outdoor unit running mode code  Off:    0,Fan  only:  1,  Cooling:  2, Heating: 3,  Forced cooling:  4.  Forced 
defrosting :A, DHW:C, Heating and DHW: d 
3  Indoor unit A capacity 
The capacity unit is horse power. If the indoor unit is not connected, the 
digital display shows the following: “――” 
(9K:1HP,12K:1.2HP,18K:1.5HP) 
4  Indoor unit B capacity 
5  Indoor unit C capacity 
6  Indoor unit D capacity 
7  Indoor unit E capacity 
8  Indoor unit A capacity demand code 
Norm code*HP 
(9K: 1HP,12K: 1.2HP,18K: 1.5HP) 
9  Indoor unit B capacity demand code 
10  Indoor unit C capacity demand code 
11  Indoor unit D capacity demand code 
12  Indoor unit E capacity demand code 
13  Outdoor unit amendatory capacity demand code
 
14  The frequency corresponding to the total indoor 
units' amendatory capacity demand 
 
15  The frequency after the frequency limit   
16  The  frequency  sending  to  compressor  control 
chip 
 
17  Indoor  unit  A  evaporator  outlet  temperature 
(T
A) 
If the temperature is lower than -9 
℃
, the digital display shows “-9.” If 
the temperature is higher than 70 
℃
, the digital display shows “70.” If 
the indoor unit is not connected, the digital display shows: “――” 
18  Indoor  unit  B  evaporator  outlet  temperature 
(T
B) 
19  Indoor  unit  C  evaporator  outlet  temperature 
(T
C) 
20  Indoor  unit  D  evaporator  outlet  temperature 
(T
D) 
21  Indoor  unit  E  evaporator  outlet  temperature 
(T
E) 
22  Indoor unit A room temperature (T
1
A) 
If the temperature is lower than 0 
, the digital display shows “0.” If the 
temperature is  higher than  50 
, the  digital display shows “50.” If the 
indoor unit is not connected, the digital display shows: “――” 
23  Indoor unit B room temperature (T
1
B) 
24  Indoor unit C room temperature (T
1
C) 
25  Indoor unit D room temperature (T
1
D) 
26  Indoor unit E room temperature (T
1
E) 
27  Indoor unit A evaporator temperature (T
2
A) 
If the temperature is lower than -9 ℃, the digital display shows “-9.” If the 
temperature is  higher than  70 ℃, the  digital display shows “70.”  If the 
indoor unit is not connected, the digital display shows: “――” 
28  Indoor unit B evaporator temperature (T
2
B) 
29  Indoor unit C evaporator temperature (T
2
C) 
30  Indoor unit D evaporator temperature (T
2
D) 
31  Indoor unit E evaporator temperature (T
2
E) 
32  Condenser pipe temperature (T3)