SERVICE MANUAL
MIDEA SUPER DC INVERTER MULTI TYPE
DC MULTI OUTDOOR UNITS
M2OD-16HFN1-Q
M2OD-18HFN1-Q
M3OD-21HFN1-Q
M3OD-26HFN1-Q
M4OD-28HFN1-Q
M4OA-36HFN1-Q
M5OC-36HFN1-Q
M5OD-42HFN1-Q
DM15-01.01.11-01en
Библиотека СОК Библиотека СОК

Questions and Answers

  • J
    Jessica WilliamsAug 6, 2025
    What to do if there is an open or short circuit of temperature sensor in my Midea M2OD-18HFN1-Q?
    • J
      Jasmine BrownAug 6, 2025
      First, check the connections between the temperature sensor and the PCB. Ensure they are properly connected. If the connections are good, measure the resistance value of the sensor. If the resistance is not normal, replace the sensor. If the resistance is normal, replace the indoor PCB.
  • T
    Tammy DelacruzAug 22, 2025
    Why is the indoor fan speed out of control on my Midea M2OD-18HFN1-Q Air Conditioner?
    • L
      lindsey92Aug 22, 2025
      A possible cause is a problem with the PCB. To check this: 1. Power on the unit and set it to fan mode at high speed. 2. Let it run for 15 seconds. 3. Measure the voltage of pin1 and pin2. If the voltage is less than 100V (for 208~240V power supply) or 50V (for 115V power supply), the PCB likely has issues and needs replacement. Alternatively, with the unit in standby, measure the voltage of pin1-pin3 and pin4-pin3 in the fan motor connector. If the voltage is not within the expected range (refer to the voltage table in the manual), the PCB needs to be replaced.

Summary

Specification

Wiring Diagram

Refrigeration Cycle Diagram

Installation Details

Air Purging with Vacuum Pump

Procedure for removing air and moisture from the refrigerant system using a vacuum pump.

Air Purging by Refrigerant

Procedure for purging air from the refrigerant system using refrigerant.

Adding Refrigerant (Longer Pipes)

Procedure for adding refrigerant when pipe length exceeds 5 meters.

Electronic Control Function

Compressor Discharge Temperature Protection

Limits frequency or stops compressor based on discharge temperature.

Low Voltage Protection

Protects the system from damage due to low input voltage.

Compressor Current Limit Protection

Limits compressor frequency if current exceeds set limits.

High Condenser Coil Temperature Protection

Stops the compressor if condenser coil temperature exceeds 65°C.

Outdoor Unit Anti-Freezing Protection

Prevents freezing by controlling indoor unit capacity based on T2B/T2.

Troubleshooting

Indoor Unit Error Code Explanation

Lists error codes for indoor units, their causes, and display patterns.

Outdoor Unit Error Code Explanation

Details error codes displayed by the outdoor unit and their corresponding LED status.

Indoor;Outdoor Unit Communication Error Troubleshooting

Flowchart for diagnosing communication errors between indoor and outdoor units.

IPM Board;Outdoor Main Board Communication Malfunction (ODU E3)

Troubleshooting steps for communication errors between IPM and outdoor main boards.

Main Parts Check