8.4.6 Opening degree of electronic expansion valve:  
Actual opening degree equals the display data divided 8 
 
8.5 Protection 
8.5.1 Three minutes delay at restart for compressor. 
8.5.2 Temperature protection of compressor discharge. 
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules: 
----If 102℃<T5<115℃, decrease the frequency to the lower level every 2 minutes till to F1. 
---If T5>115 ℃ for 10 seconds, the compressor will stop and restart till T5<90℃. 
8.5.3 Low voltage protection 
VOLLIMT1
VOLTAGE
No limit
VOLLIMT2
VOLLIMT3
Off
VOLFRE2
VOLFRE1
VOLREL1
VOLREL2
VOLREL3
 
Model  VOLLIMT1  VOLLIMT2  VOLLIMT3  VOLREL1  VOLREL2  VOLREL3  VOLFRE1  VOLFRE2 
M2OC-18HRDN1-M  230  200  120  260  210  135  62  54 
M3OC-27HRDN1-M  245  220  120  265  240  135  78  45 
M4OC-36HRDN1-M  200  185  120  210  195  135  54  42 
Note: if the low voltage protection occurs and not resumes within 3min, it will keep the protection always 
after restart the machine.  
 
8.5.4 Compressor current limit protection 
If the compressor current exceeds the current limit value for 10 seconds, the compressor frequency will be 
limited as below table. 
Cooling mode: 
Current frequency(Hz)  Current limit value(A)  Frequency limit 
COOL_F10  ICOOLLMT6 
Decrease the frequenc
COOL_F4 for 3 minutes. 
 
After that, the frequency will be adjusted according to the 
capacity demand and rise to the upper level every 3 
minutes 
(When the frequency>COOL_F4 via capacity demand). 
COOL_F9  ICOOLLMT5 
COOL_F8  ICOOLLMT4 
COOL_F7  ICOOLLMT3 
COOL_F6  ICOOLLMT2 
COOL_F5  ICOOLLMT1 
If the current frequency is lower than COOL_F4, the frequency will not be limited. 
After 10s of the compressor start, if the current>ICOOL,the AC will display the failure for 30 seconds and stop. The AC will restart 3 
minutes later. 
Heating mode: 
Current frequency(Hz)  Current limit value(A)  Frequency limit 
HEAT_F12  IHEATLMT8  Decrease the frequency to HEAT_F4 and run at HEAT_F4 
for 3 minutes. 
 
After that, the frequency will be adjusted according to the 
capacity demand and rise to the upper level every 3 
minutes 
HEAT_F11  IHEATLMT7 
HEAT_F10  IHEATLMT6 
HEAT_F9  IHEATLMT5 
HEAT_F8  IHEATLMT4