8.12 Outdoor fan speed control
There is one fan with two-speed, the fan speed is controlled according ambient temp. After
the compressor stop, 30 seconds later the fan stops.
When cooling:
> 27 High speed
Ambient temp.rise
<27 Low speed
>25 High speed Ambient
temp.decline
<25 Low speed
When heating:
> 14 Low speed
Ambient temp.rise
<14 High speed
>12 Low speed Ambient
temp.decline
<12 High speed
8.13 Oil return function
If operation frequency is lower than 54Hz in 2 hours consecutively, it will be increased to
62Hz for 3 minutes. Then it recovers to the former operation frequency.