Meanwhile the maximum running frequency will
be adjusted according to the outdoor ambient
temp.
43
41
38
T4LimFre1_ADD
No limit
T4LimFre2_ADD
T4LimFre3_ADD
42
39
37
49
46
T4LimFre4_ADD
T4LimFre5_ADD
48
45
Heating mode
Plus all the indoor capacity request together,
then modify it by T4
When there’s only one indoor unit
When there’re more than one indoor unit
Note: The final result is integer.
Then modify it according to T2
average(correction):
Note:Average value of T2:Sum T2 value of all
indoor units)/(indoor units number
According to the final capacity request to
confirm the operating frequency, as following
table.
Amendatory
capacity
demand.
Heating capacity improved in low ambient
heating
In heating mode, when
T2<T2_ExitT4LowFre_ADD , and T4<-4 ℃,
there’s frequency elevation:
elevated frequency= Recent frequency * 110%
When T2> T2_ExitT4LowFre_ADD-2 and T4>-6,
the highest frequency can’t exceed F17
When T2> T2_ExitT4LowFre_ADD-4 and T4>-8,
the highest frequency can’t exceed F18
When T2> T2_ExitT4LowFre_ADD-6 and T4>-10,
the highest frequency can’t exceed F19