66 Multi DC inverter R410A. Outdoor unit
11.3.2.9 High temperature protection of condenser (ODU P5)
When outdoor pipe temperature is more than 65°C, the unit will stop, and unit runs again when outdoor pipe
temperature less than 52°C.
Hightemperatureprotectionof
condenser
Check whether the
condenser temperature is
Higher than 65°C
Yes
Check whether the
resistance of condenser
temp. sensor is normal
refertotheAppendix 1
Replacethetemperaturesensor
No
No
Check whether the outdoor
ambient temperature is
higher than 50℃
No
StoptheunitYes
Checkiftheoutdoorunit
ventilationisgood
Yes
Make the outdoor unit ventilate well
Check whether the heat
exchanger is dirty
No
Clean the heat exchangerYes
Check whether the refrigerant
system is ok
Replace outdoor main
board
No
Refrigerantisnotenoughaddthe
refrigerant
No
Checkiftheoutdoorfanruns
properly
pleaserefertothesolutionoffan
speedhasbeenoutofcontrol
malfunction.Findoutthecauseand
haveitsolved.
No
Yes
No
CorrecttheconnectionNo
Yes
Checktheconnection
betweentemperature
sensorandPCB.
Yes