7.4.2.6 E6 (PFC module protection) error diagnosis and solution.  
When the voltage signal that PFC sends to main control board 
is abnormal, the display LED will show “E6” and AC will turn 
off. 
 
PFC module protection
Check whether the 
connecting line between 
main board and the PFC 
module(IPM module) is 
connected tightly
Yes
Check whether the voltage 
range of P-N on IPM 
module is normal? DC277-
356V for 18-27KBtu/h; 
DC277-410V for 36KBtu/h
No
Check  whether  the 
inductance  of  PFC  module 
is good? If the inductance is 
good,  the  resistance  of  the 
two ports is 0
Yes
Replace the inductance
No
Connect it tightly, check 
normal or not
Replace the outdoor main board
Yes
Yes
No
No
Replace the PFC module(IPM 
module)
Trouble is solved