7.4.2.14. High temperature protection of compressor top(IDU P2/ODU P0) 
Check if the air flow system 
of indoor and outdoor units 
are obstructed?
Clear up the air inlet and outlet or the heat 
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Turn off the power supply and turn 
it on 10 minutes later.
Check  if the temperature 
of compressor Top
Is  more than 90℃?
No
Check if the refrigerant 
system
 is normal?
Repair the refrigerant 
system .
Replace the outdoor control PCB.
Yes
Check if all the connection, especially 
the connection of OLP (Over Load 
Protector) sensor is good.
Correct the connection.No
Measure  the  resistance 
between the two ports of 
the OLP. Is it zero?
Yes
Replace the OLP.No
Replace the outdoor control PCB.
Yes
No