MCAC-PDSM-2013-04 Midea Precision AC Technical Manual-Down Delivery Series
29
Outdoor coil
(Single
outdoor unit)
No. of rows \ 3
Tube pitch(a)×row pitch(b) mm 25.4×22
Fin spacing mm 2.2
Fin type \ Hydrophilic aluminum fin
Pipe outside dia. and type mm
Ф9.52
Inner grooved copper pipe
Coil (W×D) mm 1,750×1,219.2
Number of circuits \ 18
Indoor air flow m
3
/h 23,300
Indoor external static pressure Pa 20
Indoor drain pipe I.D. mm Ф30
Indoor noise level dB(A)
≤72
Outdoor noise level dB(A)
≤66
Refrigerant
Type \ R410A
Recharged (After installation) g 17,000×2
Control \ Thermostatic expansion valve
Maximum refrigeration pipe pressure MPa 4.4
Refrigerant
pipe
Max. pipe length m 60
Max. difference in level (O.U. up) m 20
Max. difference in level (O.U.
down)
m 5
Connection
wire
Indoor power wire mm
2
3×10.0mm
2
(A,B,C)+2×6.0mm
2
(N,GND)
Outdoor power wire mm
2
(4×1.0mm
2
)+ (4×1.0mm
2
)
Signal wire mm
2
(4×1.0mm
2
)+ (4×1.0mm
2
)
Filter \ G4
Indoor unit
Net dimension (W×H×D) mm 2,685×1,971×870
Net weight kg 920
Outdoor unit
(Single)
Net dimension (W×H×D) mm 1,980×1,290×690(No include supporting bar)
Net weight kg 170
Notes:
1. The nominal cooling capacity is based on the following conditions. Indoor temperature: 24°CDB, 17°CWB;
Outdoor temperature: 35°CDB, pipe length is 10 meters.
2. The noise is measured in the semi suppression lab.