Check that cabling will not be subject to wear, corrosion, excessive pressure, 
vibration, sharp edges or any other adverse environmental effects. The check 
shall also take into account the effects of aging or continual vibration from 
sources such as compressors or fans.
9. Cabling
Under no circumstances shall potential sources of ignition be used in the searching 
for or detection of refrigerant leaks. A halide torch (or any other detector using a 
naked flame) shall not be used.
The following leak detection methods are deemed acceptable for systems 
containing flammable refrigerants. Electronic leak detectors shall be used to detect
flammable refrigerants, but the sensitivity may not be adequate, or may need 
re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) 
Ensure that the detector is not a potential source of ignition and is suitable for 
the refrigerant used. Leak detection equipment shall be set at a percentage of the 
LFL of the refrigerant and shall be calibrated to the refrigerant employed and the 
appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids 
are suitable for use with most refrigerants but the use of detergents containing 
chlorine shall be avoided as the chlorine may react with the refrigerant and 
corrode the copper pipe-work. If a leak is suspected, all naked flames shall be 
removed/ extinguished. If a leakage of refrigerant is found which requires brazing, 
all of the refrigerant shall be recovered from the system, or isolated (by means of 
shut off valves) in a part of the system remote from the leak. 
Removal of refrigerant shall be according to Removal and evacuation.
10.Detection of flammable refrigerants
When breaking into the refrigerant circuit to make repairs—or for any other purpose 
- conventional procedures shall be used. However, for flammable refrigerants it is
important that best practice be followed, since flammability is a consideration. 
The following procedure shall be adhered to:
-Safely remove refrigerant following local and national regulations; 
-Evacuate; 
-Purge the circuit with inert gas (optional for A2L); 
-Evacuate (optional for A2L);
-continuously flush or purge with inert gas when using flame to open circuit; and 
-open the circuit. 
The refrigerant charge shall be recovered into the correct recovery cylinders if 
venting is not allowed by local and national codes. For appliances containing 
flammable refrigerants, the system shall be purged with oxygen-free n flammable 
refrigerants. This process might compressed air or oxygen shall not be used for 
purging refrigerant systems. 
For appliances containing flammable refrigerants, refrigerants purging shall be 
achieved by breaking the vacuum in the system with oxygen-free nitrogen and 
continuing to fill until the working pressure is achieved, then venting to atmosphere, 
and finally pulling down to a vacuum (optional for A2L). This process shall be 
repeated until no refrigerant is within the system (optional for A2L). When the final 
oxygen-free nitrogen charge is used. the system shall be vented down to 
atmospheric pressure to enable work to take place. The outlet for the vacuum 
pump shall not be close to any potential ignition sources, and ventilation shall 
be available.
11.Removal and evacuation
In addition to conventional charging procedures, the following requirements shall be 
followed. Ensure that contamination of different refrigerants does not occur when 
using charging equipment. Hoses or lines shall be as short as possible to minimise 
the amount of refrigerant contained in them. Cylinders shall be kept in an appropriate 
position according to the instructions. Ensure that the refrigeration system is earthed 
prior to charging the system with refrigerant. Label the system when charging is 
complete (if not already). Extreme care shall be taken not to overfill the refrigeration 
system. Prior to recharging the system it shall be pressure tested with OFN. The 
system shall be leak tested on completion of charging but prior to commissioning. 
A follow up leak test shall be carried out prior to leaving the site.
12.Charging procedures