Aqua Tempo Super II
201902 17
Part 2 - Engineering Data
Table 2-1.2: Specifications
kW
30 60
Model name
MC-SU30M-RN1L MC-SU60M-RN1L
Power supply V/Ph/Hz
380-415/3/50
Cooling
1
Capacity kW
28.2 55
Rated input kW
10.93 22.54
EER
2.58 2.44
SEER
3.72 3.73
Heating
2
Capacity kW
30.8 60
Rated input kW
10.62 21.2
COP
2.90 2.83
SCOP
3.27 3.45
Seasonal space heating energy efficiency class
A+ A+
Max. running current A
19.7 36.9
Air side heat
exchanger
Type
Finned tube Finned tube
Fan motor type
DC motor DC motor
Fan motor quantity
1 2
Air flow rate
12,500 24,000
Water side heat
exchanger
Type
Plate Plate
Volume L 2.44 5.17
Water flow m
3
/h 5 9.8
Pump head m 18 15
Water pressure drop kPa 55 61
Refrigerant system
Refrigerant type R410A R410A
Refrigerant charge kg 10.5 17.0
Throttle type EXV EXV + Capillary
Sound power level dB(A) 78 87
Sound pressure level
3
dB(A) 68 73
Net dimensions (W×H×D) mm 1870×1175×1000 2220×1325×1055
Packed dimensions (W×H×D) mm 1910×1225×1035 2250×1370×1090
Net/Gross weight kg 335/345 515/525
Pipe connections Water inlet/outlet mm DN40 DN50
Controller Wired controller Wired controller
Operating temperature
range
Cooling °C -10 to 43 -10 to 43
Heating °C -15 to 30 -15 to 30
Water outlet
temperature range
Cooling
4
°C 5 to 20 5 to 20
Heating °C 25 to 55 25 to 55
Notes:
1. Cooling: Chilled water inlet/outlet temp.12/7°C; outdoor ambient temp. 35°C DB.
2. Heating: Warm water inlet/outlet temp. 40/45°C; outdoor ambient temp. 7°C DB/6°C WB.
3. Sound pressure level is measured at a position 1m in front of the unit and 1.1m above the floor in a semi-anechoic chamber.
4. Capacity and efficiency data calculated in accordance with EN14511.