17.4.7 Water-level alarm malfunction diagnosis and solution
Error Code
EE
Malfunction conditions
If the sampling voltage is not 5V, the LED will display the
failure code.
Possible causes
Wiring mistakes
Faulty water-level switch
Faulty water pump
Faulty indoor PCB
If the water-level switch
is inserted well?
If the water-level switch
is inserted well?
No
Insert the water-level switch well
Insert the water-level switch well
If the water-level switch
is broken?
If the water-level switch
is broken?
Yes
Replace the water-level switch
Replace the water-level switch
Replace the water pump, If
malfunction is still not
solved
Replace the water pump, If
malfunction is still not
solved
Yes
No
Yes
Replace the indoor main PCB
Replace the indoor main PCB
Power off, then restart the unit 3 minutes
later. Is it still displaying the error code?
Power off, then restart the unit 3 minutes
later. Is it still displaying the error code?
Yes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MCA3U-12HRFN1-M(C) and is the answer not in the manual?

Midea MCA3U-12HRFN1-M(C) Specifications

General IconGeneral
BrandMidea
ModelMCA3U-12HRFN1-M(C)
CategoryAir Conditioner
LanguageEnglish

Related product manuals