G. Micro-switch SW8 is for setting the master or slave unit when the unit is in twin connection.
Range: Master no slave (Normal 1 drive 1 connection), Master (2 positions without difference), Slave
H.Micro-switch S1 and dial-switch S2 are for address setting when you want to control this unit by a
central controller.
Range: 00-63
I.Dial-switch ENC1: The indoor PCB is universal designed for whole series units from 7K to 68K. This
ENC1 setting will tell the main program what size the unit is.
NOTE: Usually there is glue on it because the switch position cannot be changed at random unless
you want to use this
PCB as a spare part to use in another unit. Then you have to select the right position to match the size
of the unit.
“20” means 2kW (7K),“105” means 10.5kW(36K), and so on.