EasyManuals Logo

Midea MDV-280(10)W/D2RN1T(C) User Manual

Midea MDV-280(10)W/D2RN1T(C)
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
V4+R VRF 50/60Hz
201608 55
Part 5 - Diagnosis and Troubleshooting
4.4 E2 Troubleshooting
Digital display output 4.4.1
Description 4.4.2
Communication error between indoor and master unit.
All units stop running.
Error code is only displayed on the master unit.
Possible causes 4.4.3
Communication wires between indoor and outdoor units not connected properly.
Indoor unit power supply abnormal.
Loosened wiring within electric control box.
Interference from high voltage wires or other sources of electromagnetic radiation.
Communication wire too long.
Damaged main PCB or electric control box communication terminals block.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MDV-280(10)W/D2RN1T(C) and is the answer not in the manual?

Midea MDV-280(10)W/D2RN1T(C) Specifications

General IconGeneral
BrandMidea
ModelMDV-280(10)W/D2RN1T(C)
CategoryAir Conditioner
LanguageEnglish

Related product manuals