EasyManua.ls Logo

Midea MDV-730(26)W/D2DN1(B)

Midea MDV-730(26)W/D2DN1(B)
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
R410A All DC Inverter V4+S Series 60Hz MCAC-VTSM-2015-09
94 Installation
1. Select indoor unit pipes from indoor unit to the nearest branch joint: a, b, c, d, e, f, g, h, i, j.
Refer to table 5, the pipes of a~j are Φ5/8(15.9)/ Φ3/8(9.53).
2. Select the main pipe L1, indoor unit main pipes L2~L9 and branch joints B~I:
The downstream indoor units of L3 are N1 and N2, with total capacity of 14×2=28kW(95.5kBtu/h). Refer to table 1, the indoor
unit main pipe L3 is Φ7/8(22.2)/ Φ3/8(9.53). The branch pipe assembly C is FQZHN-02D.
The downstream indoor unit of L4 is N3 and N4, with total capacity of 14×2=28kW(95.5kBtu/h). Refer to table 1, the indoor unit
main pipe L4 is Φ7/8(22.2)/ Φ3/8(9.53). The branch pipe assembly D is FQZHN-02D.
The downstream indoor unit of L7 is N6 and N7, with total capacity of 7.1×2=14.2kW(48.5kBtu/h). Refer to table 1, the indoor
unit main pipe L7 is Φ5/8(15.9)/ Φ3/8(9.53). The branch pipe assembly G is FQZHN-01D.
The downstream indoor units of L9 are N9 and N10, with total capacity of 5.6×2=11.2kW(38.2kBtu/h). Refer to table 1, the
indoor unit main pipe L9 is Φ5/8(15.9)/ Φ3/8(9.53). The branch pipe assembly I is FQZHN-01D.
The downstream indoor units of L2 are N1, N2, N3 and N4, with total capacity of 14×4=56 kW (191.1kBtu/h). Refer to table 1,
the indoor unit main pipe L2 is Φ1-1/8(28.6)/ Φ5/8(15.9). The branch pipe assembly B is FQZHN-03D.
The downstream indoor unit of L6 is N5, N6 and N7, with total capacity of 14+7.1×2=28.2kW(96.2kBtu/h). Refer to table 1, the
indoor unit main pipe L6 is Φ7/8(22.2)/ Φ3/8(9.53). The branch pipe assembly F is FQZHN-02D.
The downstream indoor units of L8 are N8, N9 and N10, with total capacity of 14+5.6×2=25.2kW(86kBtu/h). Refer to table 1,
the indoor unit main pipe L8 is Φ7/8(22.2)/ Φ3/8(9.53). The branch pipe assembly H is FQZHN-02D.
The downstream indoor units of L5 are N5, N6, N7, N8, N9 and N10, with total capacity of
14×2+7.1×2+5.6×2=53.4kW(182.2kBtu/h). Refer to table 1, the indoor unit main pipe L2 is Φ1-1/8(28.6)/ Φ5/8(15.9). The
branch pipe assembly E is FQZHN-03D.
3. Select main pipe L1 and branch joint A:
For outdoor units with capacity of 40HP, the equivalent length of all pipes in this system is larger than 295ft(90m), refer to table
2, the main pipe L1 is Φ1-1/2(38.1)/ Φ7/8(22.2), the branch pipe assembly A is FQZHN-04D.
The downstream indoor units of L1 are N1~N10, with total capacity of 14×6+7.1×2+5.6×2=109.4kW(373.3kBtu/h). Refer to
table 1, the main pipe L1 is Φ1-1/2(38.1)/ Φ3/4(19.1). So we finally select the larger pipeΦ1-1/2(38.1)/ Φ7/8(22.2) as main pipe
L1.
4. Outdoor unit connection pipe (g1, g2, g3, G1,L+M) selection (refer to table3, table 4)
The pipe g1 is connected to 10HP outdoor unit. Refer to table3, the diameter of g1 is Φ1(25.4) /Φ1/2(12.7).
The pipe g2 is connected to 14HP outdoor unit. Refer to table3, the diameter of g2 isΦ31.8(Φ1-1/4) /Φ15.9(Φ5/8).
The pipe g3 is connected to 16HP outdoor unit. Refer to table3, the diameter of g3 is Φ1-1/4(31.8)/ Φ5/8(15.9).
Refer to table3, the diameter of G1 isΦ38.1(Φ1-1/2)/ Φ3/4(19.1).
The quantity of combined outdoor units is three. Refer to table4, the outdoor branch assembly is L+M: FQZHW-03N1D.
3.4 Branch joint dimension
3.4.1 Indoor branch joint dimension
Branch model
Gas side joints
Liquid side joints
FQZHN-01D
ID:12.7
(ID:15.9)
OD:19.1
ID:19.1
OD:19.1
ID:19.1
ID:15.9
ID:12.7
(ID:15.9)
OD:19.1
OD:12.7
ID:9.5
ID:9.5
ID:6.4
OD:9.5
ID:6.4
OD:9.5
ID:9.5

Table of Contents

Related product manuals