MCAC-VTSM-2014-09 R410A All DC Inverter Mini VRF
Troubleshooting 77
sensor, find that T4 thermo-bulb is earth-continuity, and further discover that the thermal cable of T4
sensor is punched by bolt, as follows:
7.4 E5: Voltage protection malfunction (for all models)
T4 sensor is worn out and
connected with sheet metal
After being reconnected, the
system becomes normal
LED displays E5
Voltage protection malfunction
Whether the input voltage is 180-260V.
NO
Replace the filter board and check whether the unit can
operate normally.
Check the power supply.
YES
Replace the main PCB
YES
OK
NO