MCAC-VTSM-2013-12 R410a Full DC Inverter Mini VRF
Troubleshooting 113
7.11 P3: Compressor current protection (for all models)
It will protect when input current is more than 30A. It will recover when input current is less than 30A.
It will recover automatically.
`
LED displays P3
Check whether the input current of the power wire is more
than 30A.
Check cooling system is normal or not.
Check whether the outdoor ambient temperature is too high.
Check whether the outdoor unit ventilates well.
Make the outdoor unit
ventilates well.
Whether the heat exchanger needs cleaning or not.
If the refrigerant pipe is blocked or not?
Remove the refrigerant pipe and then use
high pressure nitrogen or refrigerant to blow
the pipe. Vacuume the pipe then add the
refrigerant again.