EasyManua.ls Logo

Midea MGC-F16W/SN1 - Electric Characteristics of Outdoor Units

Midea MGC-F16W/SN1
94 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specification MCAC-TSM-2008-02
20 Installation
6. Electric Characteristics
Outdoor Unit Power Supply Compressor OFM
Model
Hz Voltage phase Min. Max. MCA TOCA MFA MSC RLA kW FLA
MGC-F05W/N1 50Hz 220-240V 1ph 198V 254V 11.25 10.8 15 36.8 8.7 0.12 1
MGC-F07W/N1 50Hz 220-240V 1ph 198V 254V 17.5 16.6 20 63 13.1 0.12 1
MGC-F09W/N1 50Hz 220-240V 1ph 198V 254V 24.5 32 35 123 19.5 0.1×2 0.8×2
MGC-F10W/N1 50Hz 220-240V 1ph 198V 254V 24.5 32 35 123 19.5 0.1×2 0.8×2
MGC-F10W/SN1 50Hz 380-415V 3ph 342V 440V 9.2 10.5 20 64 7.3 0.1×2 0.8×2
MGC-F12W/SN1 50Hz 380-415V 3ph 342V 440V 12.12 11.5 15 66 8.22 0.1×2 0.8×2
MGC-F14W/SN1 50Hz 380-415V 3ph 342V 440V 10.2 25 15 67 9.77 0.1×2 0.8×2
MGC-F16W/SN1 50Hz 380-415V 3ph 342V 440V 15.75 15 20 73 11.6 0.1×2 0.8×2
Remark:
MCA: Min. Current Amps. (A)
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Max. Starting Amps. (A)
RLA: Rated Current Amps. (A)
OFM: Outdoor Fan Motor
FLA: Full Load Amps. (A)
kW: Rated Motor Output. (kW)

Table of Contents

Related product manuals