Specification MCAC-TSM-2008-02
36 Installation
MGC-F16W/SN1
Ta.
U.R.87%
Tw 35 40 45 50
Pt 10.5 10.4 10.3 -
Pa 3.6 4.0 4.5 -
Pat 3.9 4.3 4.8 -
Qc 1.8 1.8 1.8 -
-5
Pc 13.9 13.9 13.8 -
Pt 12.8 12.7 12.6 12.5
Pa 3.7 4.1 4.6 5.1
Pat 4.0 4.4 4.9 5.4
Qc 2.2 2.2 2.2 2.2
0
Pc 20.2 20.1 20 19.9
Pt 15.6 15.5 15.5 15.4
Pa 3.8 4.2 4.7 5.3
Pat 4.1 4.5 5.0 5.6
Qc 2.7 2.7 2.7 2.7
7
Pc 30.2 30.1 30 30
Pt 16.9 16.8 16.7 16.6
Pa 3.9 4.3 4.8 5.3
Pat 4.2 4.6 5.1 5.6
Qc 3.0 3.0 3.0 3.0
10
Pc 35.4 35.2 35 34.8
Pt 19 18.9 18.8 18.7
Pa 4.0 4.4 4.9 5.5
Pat 4.3 4.7 5.2 5.7
Qc 3.2 3.2 3.2 3.2
15
Pc 46.2 45.6 45 44.4
Note:
Ta: outside air temperature (°C)
Tw : evaporator water outlet temperature (°C)
Pt: heating capacity (kW)
Pa: compressor power input (kW)
Pat: total power input (kW)
Qc: condenser water flow (m3/h)
ΔPc: evaporator pressure drop (kPa)
- : Exceed operating limits