Specification MCAC-TSM-2008-02
62 Installation
12. Error code Er90
Values display indication Er90
Refer to the instruction manual: Alarm history records exceeded 99 times
In this condition, it must be recovered by manual reset, please do as follow on the
control interface
Press [esc + set] in the main screen. The label ‘PAr’ will appear.
Scroll with ‘UP’ and ‘DOWN’ to find the ‘FnC’ label.
Press ‘set’. The label ‘dEF’ will appear. Scroll with ‘UP’ and ‘DOWN’ to find the ‘EUr’ label.
as the following picture.
Press the “set” key for 3 seconds [set]
The ‘YES’= label appears to indicate that the alarm log has been deleted. The trouble
is solved.